Background image shows a close up of an ohmmeter. The title ESD Flooring: Why Some Carpet Cannot Be Grounded is displayed in bold white text against a rectangle of dark blue grey at the bottom of the image and just above is the text "Static Shorts with StaticWorx - Right from the Den" and the StaticWorx logo
Play Video
Background image shows a close up of an ohmmeter. The title ESD Flooring: Why Some Carpet Cannot Be Grounded is displayed in bold white text against a rectangle of dark blue grey at the bottom of the image and just above is the text "Static Shorts with StaticWorx - Right from the Den" and the StaticWorx logo
Play Video

ESD Flooring: Why Some Carpet Cannot Be Grounded

Static Shorts with StaticWorx: Right from the den

We’re back in the den with Dave Long today for another episode of Static Shorts with StaticWorx: Right from the den.

Today, Dave’s talking about conductivity and testing the electrical resistance of regular, static-dissipative, and highly conductive carpet.

Today, what we've done is we've shown you why it's important, when you write a specification, that you actually require the supplier to test the floor after the floor is installed, and in writing, tell you what they got for measurements. You saw how easy the measurements were. It's not that difficult.

Hi I’m Dave Long, from StaticWorx. Just like the video we made yesterday, I’m at home again. I’m guessing you are too.

So what I discussed yesterday was the difference between low kV carpet, and static-dissipative carpet. Today we’re going to continue that discussion, but today, we’re going to talk about conductivity.

So what I’ve done, is I’ve gathered together a bunch of meters that measure electrical resistance. So this is what’s called a digital ohm meter. I have a handheld meter, with two blades on the bottom, where we measure the resistance between the blades. And I have an analog meter, which represents the electrical resistance by these various numbers that are on here. And for those of you who like math, the numbers are logarithmic. So it goes from 10 to the 3rd (10E3) to 10 to the 4th (10E4), to 10 to the 5th (10E5), all the way up to 10 to the 13th (10E13). And all that means is that at 10 to the 3rd (10E3), we’re talking about something that’s 1000 ohms. At 10 to the 4th , we’re talking about 10,000. At 10 to the 5th (10E5) we’re talking about 100,000. So each number, the actual numerical representation grows by a factor of 10.

So like yesterday, I have low kV carpet. Which if you look closely at the bottom of it, has a light-colored material backing. And I have static-dissipative carpet, where the backing is a little bit darker than this material. And, here’s a piece of low kV carpet. You can see the big difference between the two colors. That’s because this has carbon in the bottom of it, which is a conductor, and this doesn’t have any.

So what I’m going to do, is I’m gonna turn on this meter. And I’m going to measure the electrical resistance, just simply between two points on the carpet tile. So when I press the button, as you can see, I’m measuring between 10 and 11. That means 10 to the 10th (10E10), to 10 to the 11th (10E11). So to give you some perspective, 10 to the 9th (10E9) is one billion. So 10 to the 10th (10E10) is 10 billion. So this has an electrical resistance of over 10 billion ohms. In order for us to call a product static safe, and for that product to be used in applications where we need to reduce static electricity, it has to measure under nine. Which is 10 to the 9th (10E9), which I just told you is a billion. So with this meter, I’m measuring something that’s clearly not acceptable.

Now I’m gonna take the two probes. Put them on the static-dissipative carpet. Make the same measurement. And I’m measuring less than 10 to the 8th (10E8). So by definition, any material that measures between six and nine, is called a static-dissipative material. If it measures less than six, it’s called a conductive material. And for those of you who are writing specifications for applications like call centers, or FAA flight towers, or server rooms, you don’t want the flooring material to measure less than 10 to the 6th (10E6). I’ll give you an example of that. Here’s a material. It’s got a black back on it. When I put the two probes on it, it measures less than 10 to the 5th (10E5). That’s a piece of conductive carpet. That would not be acceptable if the requirement for the application called for static dissipative. So what we’ve got is regular carpet, highly conductive carpet, and static-dissipative carpet.

Let’s pull out the probes, let’s plug them into a different meter. The reason the meter says good, it doesn’t mean there’s anything special going on, the battery’s good. And hit test. And, the conductive carpet is measuring six times 10 to the 4th (10E4). If the application calls for a material that measures greater than 10 to the 6th (10E6), this is two orders of magnitude too conductive. Let’s put the probes on the static-dissipative carpet. Let’s hit test again. 5.7, 5.8, 5.9, six. Six times 10 to the 7th (10E7). Pretty close to the same reading we got with the analog meter. This falls right in the middle of static dissipative. If the application were to call for a static-dissipative carpet, you’ve got your winner. Now let’s take it, and put it on the regular carpet. And by the way, when I say regular carpet, this is commercial grade carpet. It’s actually the same carpet style as the one I just tested. But it doesn’t have static-dissipative properties. When I test it, it measures over 10 to the 10th (10E10). I already told you, anything above 1.0 times 10 to the 9th (10E9) is unacceptable. So low kV carpet, which is what this is, doesn’t have any conductivity. What that means, is you can’t ground it. If you can’t ground a floor, you don’t have a solution to a static problem.

So yesterday I showed you how I could charge up this metal plate, and discharge it to these materials. Today, I showed you why that metal plate would not discharge to this, and why it would discharge to this. The next time we talk, I’ll show you other materials, hard surface materials, rubber, vinyl, epoxy. But for today, what we’ve done is we’ve shown you why it’s important, when you write a specification, that you actually require the supplier to test the floor after the floor is installed, and in writing, tell you what they got for measurements. You saw how easy the measurements were. It’s not that difficult. Thank you for listening.

Hi I’m Dave Long, from StaticWorx. Just like the video we made yesterday, I’m at home again. I’m guessing you are too.

So what I discussed yesterday was the difference between low kV carpet, and static-dissipative carpet. Today we’re going to continue that discussion, but today, we’re going to talk about conductivity.

So what I’ve done, is I’ve gathered together a bunch of meters that measure electrical resistance. So this is what’s called a digital ohm meter. I have a handheld meter, with two blades on the bottom, where we measure the resistance between the blades. And I have an analog meter, which represents the electrical resistance by these various numbers that are on here. And for those of you who like math, the numbers are logarithmic. So it goes from 10 to the 3rd (10E3) to 10 to the 4th (10E4), to 10 to the 5th (10E5), all the way up to 10 to the 13th (10E13). And all that means is that at 10 to the 3rd (10E3), we’re talking about something that’s 1000 ohms. At 10 to the 4th , we’re talking about 10,000. At 10 to the 5th (10E5) we’re talking about 100,000. So each number, the actual numerical representation grows by a factor of 10.

So like yesterday, I have low kV carpet. Which if you look closely at the bottom of it, has a light-colored material backing. And I have static-dissipative carpet, where the backing is a little bit darker than this material. And, here’s a piece of low kV carpet. You can see the big difference between the two colors. That’s because this has carbon in the bottom of it, which is a conductor, and this doesn’t have any.

So what I’m going to do, is I’m gonna turn on this meter. And I’m going to measure the electrical resistance, just simply between two points on the carpet tile. So when I press the button, as you can see, I’m measuring between 10 and 11. That means 10 to the 10th (10E10), to 10 to the 11th (10E11). So to give you some perspective, 10 to the 9th (10E9) is one billion. So 10 to the 10th (10E10) is 10 billion. So this has an electrical resistance of over 10 billion ohms. In order for us to call a product static safe, and for that product to be used in applications where we need to reduce static electricity, it has to measure under nine. Which is 10 to the 9th (10E9), which I just told you is a billion. So with this meter, I’m measuring something that’s clearly not acceptable.

Now I’m gonna take the two probes. Put them on the static-dissipative carpet. Make the same measurement. And I’m measuring less than 10 to the 8th (10E8). So by definition, any material that measures between six and nine, is called a static-dissipative material. If it measures less than six, it’s called a conductive material. And for those of you who are writing specifications for applications like call centers, or FAA flight towers, or server rooms, you don’t want the flooring material to measure less than 10 to the 6th (10E6). I’ll give you an example of that. Here’s a material. It’s got a black back on it. When I put the two probes on it, it measures less than 10 to the 5th (10E5). That’s a piece of conductive carpet. That would not be acceptable if the requirement for the application called for static dissipative. So what we’ve got is regular carpet, highly conductive carpet, and static-dissipative carpet.

Let’s pull out the probes, let’s plug them into a different meter. The reason the meter says good, it doesn’t mean there’s anything special going on, the battery’s good. And hit test. And, the conductive carpet is measuring six times 10 to the 4th (10E4). If the application calls for a material that measures greater than 10 to the 6th (10E6), this is two orders of magnitude too conductive. Let’s put the probes on the static-dissipative carpet. Let’s hit test again. 5.7, 5.8, 5.9, six. Six times 10 to the 7th (10E7). Pretty close to the same reading we got with the analog meter. This falls right in the middle of static dissipative. If the application were to call for a static-dissipative carpet, you’ve got your winner. Now let’s take it, and put it on the regular carpet. And by the way, when I say regular carpet, this is commercial grade carpet. It’s actually the same carpet style as the one I just tested. But it doesn’t have static-dissipative properties. When I test it, it measures over 10 to the 10th (10E10). I already told you, anything above 1.0 times 10 to the 9th (10E9) is unacceptable. So low kV carpet, which is what this is, doesn’t have any conductivity. What that means, is you can’t ground it. If you can’t ground a floor, you don’t have a solution to a static problem.

So yesterday I showed you how I could charge up this metal plate, and discharge it to these materials. Today, I showed you why that metal plate would not discharge to this, and why it would discharge to this. The next time we talk, I’ll show you other materials, hard surface materials, rubber, vinyl, epoxy. But for today, what we’ve done is we’ve shown you why it’s important, when you write a specification, that you actually require the supplier to test the floor after the floor is installed, and in writing, tell you what they got for measurements. You saw how easy the measurements were. It’s not that difficult. Thank you for listening.

Get in Touch

The form below will help us better understand your needs and get you as quickly as possible to the right person. We look forward to helping you solve your static problem! 

You can expect a response within 24 hours. For faster service, please give us a call: 617-923-2000

Visit our privacy policy to find out how we process data.

Twitter
LinkedIn
Facebook
Reddit
Pinterest
Email

More Static Shorts Episodes

Background graphic is a still from the StaticWorx GroundSafe ESD Flooring – Your Trusted Partner explainer animation. In the foreground at the bottom are two boxes. The top is a bright blue with the StaticWorx logo and "GroundSafe ESD Flooring" underneath in white. The second is a dark blue-gray and includes the text in white: “GroundWorx ESD Flooring – Your Trusted Partner”
Play Video

StaticWorx high-performance static-control floors protect electronic components, explosives, and high-speed computers from damage caused by static electricity. ESD flooring is part of a system. Choices should always be based on objective, researched evidence. When you partner with us, we look at all possible items that may need to integrate with the floor, and, focusing on your goals and objectives, help you find the right floor for your application.